VAV-PRC011M-EN 39
Single-Duct VAV Terminal Units
Electrical Data
Table 28. VCEF electric coil kW guidelines - minimum to maximum
Single-Phase Voltage Three-Phase Voltage
Inlet Size Stages 120V 208V/240V 277V 347V 480V 208V 480V 575V
(a)
380V/50 Hz
04
1
2
3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
-
1.0
-
-
1.0
1.0
1.0
1.0
1.0
-
-
-
-
1.0
1.0
-
05
1
2
3
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.5-2.5
1.0-2.5
2.0-2.5
2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
1.0-2.5
2.5
1.5-2.5
1.5-2.5
-
1.0-2.5
1.0-2.5
2.0-2.5
06
1
2
3
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.5-4.0
1.0-4.0
2.0-4.0
2.5-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0-4.0
1.0.4.0
2.5-4.0
1.5-4.0
1.5-4.0
4.0
1.0-4.0
1.0-4.0
2.0-4.0
08
1
2
3
1.0-5.0
1.0-5.0
1.0-5.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
(b)
1.5-7.0
1.0-7.0
1.5-7.0
2.5-7.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
1.0-7.0
2.5-7.0
1.5-7.0
1.5-7.0
3.5-7.0
(a)
1.0-7.0
1.0-7.0
1.5-7.0
10
1
2
3
1.0-5.0
1.0-5.0
1.0-5.0
1.0-9.0
1.0-9.0
1.0-9.0
1.0-11.0
1.0-11.0
1.0-11.0
1.0-11.0
1.0-11.0
1.5-11.0
1.0-11.0
1.0-11.0
1.5-11.0
1.0-11.0
1.0-11.0
1.0-11.0
1.0-11.0
1.0-11.0
1.5-11.0
1.5-11.0
1.5-11.0
2.5-11.0
1.0-11.0
1.0-11.0
1.5-11.0
12
1
2
3
1.0-5.0
1.0-5.0
1.0-5.0
1.0-9.0
1.0-9.0
1.0-9.0
1.0-13.0
1.0-13.0
1.0-13.0
1.0-16.0
1.0-16.0
1.5-16.0
1.0-16.0
1.0-16.0
1.5-16.0
1.0-15.0
1.0-15.0
1.0-15.0
1.0-16.0
1.0-16.0
1.5-16.0
1.5-15.0
1.5-15.0
2.0-15.0
1.0-16.0
1.0-16.0
1.5-16.0
14
1
2
3
1.0-5.0
1.0-5.0
1.0-5.0
1.0-9.0
1.0-9.0
1.0-9.0
1.0-13.0
1.0-13.0
1.0-13.0
1.0-16.0
1.0-16.0
1.5-16.0
1.0-22.0
1.0-22.0
1.5-22.0
1.0-15.0
1.0-15.0
1.0-15.0
1.0-22.0
1.0-22.0
1.5-22.0
1.5-22.0
1.5-22.0
2.0-22.0
1.0-22.0
1.0-22.0
1.5-22.0
16
1
2
3
1.0-5.0
1.0-5.0
1.0-5.0
1.0-9.0
1.0-9.0
1.0-9.0
1.0-13.0
1.0-13.0
1.0-13.0
1.0-16.0
1.0-16.0
1.5-16.0
1.0-22.0
1.0-22.0
1.5-22.0
1.0-15.0
1.0-15.0
1.0-15.0
1.0-30.0
1.0-30.0
1.5-30.0
1.5-30.0
1.5-30.0
2.0-30.0
1.0-26.0
1.0-26.0
1.5-26.0
24 x 16
1
2
3
1.5-5.0
1.5-5.0
1.5-5.0
1.0-9.0
1.0-9.0
1.0-9.0
1.0-13.0
1.0-13.0
1.0-13.0
1.0-16.0
1.0-16.0
1.5-16.0
1.0-22.0
1.0-22.0
1.5-22.0
1.5-15.0
1.5-15.0
1.5-15.0
1.0-34.0
1.0-34.0
1.5-34.0
1.5-42.0
1.5-42.0
2.0-42.0
1.0-26.0
1.0-26.0
1.5-26.0
Notes:
1. Coils available with 24-volt magnetic or mercury contactors, load carrying P.E switches, and P.E. switch with magnetic or mercury contactors.
2. Available kW increments are by 0.5 kW from 1.0 to 8.0 kW, by 1.0 kW from 9.0 to 18.0 kW, and by 2.0 kW from 18.0 to 46.0 kW.
3. Each stage will be equal in kW output.
4. All heaters contain an auto-thermal cutout and a manual-reset cutout.
5. The current amp draw for the heater elements is calculated by the formula at the end of this section.
6. The maximum allowable kW is based on the largest kW possible per a voltage and the minimum airflow per an inlet size and kW.
7. SCR not available with 575V.
(a) No 5.5 kW available.
(b) No 6.5 kW available.