CLCH-SVN05A-EN 5
Installation Considerations
Installation Considerations
• Isolation rails should not be installed on top of Trane roof curbs. If isolation rails or isolation
curbs are required, the entire curb system should be supplied by a specialty curb company.
Note: For proper operation, the unit must be supported around the entire unit base perimeter.
The roof curb must be supported along its entire perimeter. The curb may be set parallel or at right
angles to roof support members. If at right angles to the support members, there must be adequate
supporting roof cross members between the ends (in the direction of airflow). Be sure the cross
members do not interfere with the connection of supply and return ducts to the unit. See Figure 2
for details.
• When mounting the unit on its roof curb, make sure that the gasketing between the roof curb
and unit base provides an airtight seal.
Note: When pulling shipping split sections together, the field-supplied gasket material may bunch
up between bases. Make certain this does not prevent tight contact between shipping
sections.
Figure 2. Unit set perpendicular to roof curb members
Discharge
Intake
Airflow
Auxillary support
loaded under curbs
Roof mounting curb
inside edge
Main roof support member
capable of supporting unit
weight
Main roof support member
or auxillary support located
under center of unit or under
section joints