16 VRF-SVX27A-EN
Installation
The hose should not be allowed to hang loose from its connection to the unit. Fasten the
hose to a wall, frame or other support as close to the unit as possible.
If increasing the height of the drain pipe is necessary to set the drain hose at a sufficient
slope, installing a vertical drain pipe within 11.8
in. (300 mm) from the drain hose port (see
A). If raised higher than 21.65
in. (550 mm), water leaks may result (see “C” in figure).
Install the air vent at least 3.04 in. (100 mm) above the highest point of the drain pipe.
Centralized Drainage
If the installation requires more than three indoor units, install the main air vent at the front of the
indoor unit that is farthest from the main drain.
It may be necessary to install individual air vents to prevent water flowing back to each indoor unit.
See figure below.
Testing the Drainage
After completing the installation, test the drainage to make sure there are no leaks:
3.28–4.92 ft
(1–1.5 m)
A = 11.8 in. (300 mm) or less
B = 3.28–4.92 ft (1–1.5 m)
C = 21.65 in. (550 mm) or less
D = 3.94 in. (100 mm) or more
E = 0.79 in. (20 mm) or more
Air vent
A
B
C
Horizontal drain pipe: more than 1/100 slope
Ceiling
D
Hanger
E
Hanger
Main drain pipe
Individual
air vent
Main air vent
Centralized horizontal drainpipe (more
than 1/100 slope)
22 in. (550 mm) or less
39–59 in. (1–1.5 m)
Ceiling