
Installation—Electrical
UV-SVN03F-EN 43
and local requirements. Refer to the following table for the
wire size range and maximum wiring distance for each
device.
Important: Do not bundle or run interconnection wiring
in parallel with or in the same conduit with
any high-voltage wires (110 V or greater).
Exposure of interconnection wiring to high
voltage wiring, inductive loads, or RF
transmitters may cause radio frequency
interference (RFI). In addition, improper
separation may cause electrical noise
problems. Therefore, use shielded wire
(Belden 83559/83562 or equivalent) in
applications that require a high degree of
noise immunity. Connect the shield to the
chassis ground and tape at the other end.
Note: Do not connect any sensor or input circuit to an
external ground connection.
Supply Power. Power supply wiring is to be connected
to terminals 1 and 2 at the junction box in the left end
pocket, below the discharge air grille.
Electric Heat (Option)
Supply Power. Supply power wiring is to be connected
to the following line terminals in the right-hand end
pocket:
• 208V or 240V, 3-phase, 3-wire system: L1, L2, and L3.
• 480V, 3-phase, 4-wire system: L1, L2, L3, and N
(neutral)
See “Wiring Diagrams,” p. 84 for a typical unit line and
interconnecting wiring diagram for electric heat coils.
Note: The supply neutral wire must be connected to the
neutral terminal block.
Operational controls and an electric heating safety device
are factory mounted. The safety device is a high temp cut-
out which de-energizes electric heating elements through
the K1 safety contactor.
DX System
A typical unit ventilator with DX coil includes an outside air
thermostat, a frost prevention thermostat, and a 24 V
transformer for condensing unit control.
Wire sizing is the same as given for the thermostat wiring
in the condensing unit installation instructions, or may be
obtained from the nameplate. The condensing unit must
be controlled by the same room thermostat that also
controls the unit ventilator.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of
conductors. Failure to use copper conductors could
result in equipment damage.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
NOTICE:
Equipment Damage!
480 V/3-Wire is NOT compatible with Trane Classroom
Unit Ventilator equipment. There must be a 4-wire
system with a separate ground. Failure to provide a 4-
wire system could result in equipment damage.
UV-SVN03_.book Page 43 Thursday, January 24, 2013 5:27 PM
Comentarios a estos manuales