12 CLCH-SVX07C-EN
Unit Dimensions and Weights
Service Clearances
A minimum clearance of the section width plus 12 inches
on the access door side of the gas heat section is
recommended for routine maintenance. This clearance
provides enough room to replace the heat exchanger in
the event of failure. The section side panels must be
removed to access the heat exchanger. Refer to Table 3 for
service clearance recommendations for the air handler.
Note: For specific dimensional and weight information, refer to the unit submittals. The dimensions and weights in this
manual are approximate. Trane has a policy of continuous product and product data improvement and reserves
the right to change design and specifications without notice.
Figure 3. Service Clearance
Table 3. Service clearance dimensions (inches)
Component 3 4 6 8 10 12 14 17 21 22 25 26 30 31 35 36 40 41 50 51 57 58 66 80 100 120
A (filter) 4848484848484848484848484848484848484848484852565858
B (coil) 48 59 59 66 77 82 87 87 95 77 95 77 109 87 115 96 128 96 141 110 141 110 156 156 170 197
C (UV Lights) 4848484848484848484848484848484848484848484852565858
C (Catalytic Air
Cleaner)
43 59 59 63 75 81 83 83 58 75 58 75 83 83 75 59 83 83 83 83 83 83 83 83 75 83
D (external starter
or VFD)
61 61 61 61 61 61 61 61 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64
D (internal starter
or VFD)
48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48
E (fan) 484848485154586160516651665866607060776677669393101101
F (gas heat - Ext
Vestibule)
n/a n/a 89 90 108 100 100 105 115 n/a 115 n/a 118 n/a 136 n/a 140 n/a 156 n/a 156 n/a 170 179 180 n/a
F (gas heat - Int
Vestibule)
n/a n/a 56 63 74 79 84 84 92 n/a 92 n/a 106 n/a 112 n/a 125 n/a 138 n/a 138 n/a 153 153 167 194
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors, coil, piping connections, motor locations, hoods, pipe cabinets, etc. Sufficient clearance
must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs,
or other high-voltage devices must be provided per NEC requirements.
Note: For specific dimensional and weight information, refer to the unit submittals. The dimensions and weights in this manual are approximate. Trane has