CXRC-SVX01F-EN 21
Start-Up and Shutdown
Start-Up
When wired properly, the unit will cycle condenser fans in
response to compressor interlock or the Intellipak
controller output.The Intellipak controller reads saturated
refrigerant temperatures and cycles the fans
appropriately.Typical wiring schematics are listed in
“Wiring Diagrams,” p. 27.
Normal Unit Shut Down
The unit can be stopped by opening the unit power supply
disconnect switch. Normally however, unit operation
stops due to interruption of the cooling demand signal by
the circuit cooling relays.The CCRC/CIRC condensing unit
should be shutdown by first shutting down the indoor
evaporative cooling unit. By stopping the indoor unit the
request for condensing has been terminated thus
stopping all condenser fans.The disconnect switch on the
CCRC/CIRC unit power supply should then be opened. Not
shutting down the evaporator unit before the condenser
unit will result in a high-pressure situation and should be
avoided if possible.
Seasonal Shut Down
If the unit will be inoperative for an extended period, lock
out unit operation by disconnecting the compressor
interlock circuits and opening and locking the main power
disconnect switch.
If desired, large amounts of liquid refrigerant can be
isolated and stored in the condenser by closing the liquid
line service valves and operating the compressors to
pump the refrigerant into the condenser and then valving
off the hot gas line near the condenser coil.
Seasonal Startup
1. Inspect the interior of the unit for debris.
2. Check control panel wiring connections for corrosion
and proper security. Check control panel door for
proper weather seal.
3. Inspect condenser fans. Blades must be secure on fan
shaft and rotate freely.
4. Inspect coil for obstructions and cleanliness. Clean coil
if required. Refer to “Maintenance.
5. Inspect low ambient dampers. Damper blades must be
properly aligned, free from obstructions and operate
freely.You may have to disconnect actuator linkage to
inspect damper movement.
6. Close unit power supply disconnect switch.
7. Allow 24 hours of crankcase operation before starting
compressors. Crankcase heaters are energized
whenever the unit disconnect is closed and the
compressors are off.
The unit should now operate properly in response to
cooling demand at the system thermostat.
WARNING
Live Electrical Components!
During installation, testing, servicing and
troubleshooting of this product, it may be necessary to
work with live electrical components. Have a qualified
licensed electrician or other individual who has been
properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical
components could result in death or serious injury.
NOTICE:
Compressor Damage!
Never manually or automatically pump down system
below 7 psig.This will cause the compressor to operate
in a vacuum and result in compressor damage.
NOTICE:
Compressor Damage!
Keep crankcase heaters on whenever refrigerant is in
the system. If crankcase heaters have not been on with
refrigerant in the system, turn the crankcase heaters on
for a minimum of 24hours before starting compressors.
Failure to follow the above could result in compressor
failure or reduced compressor life.