Trane Modular 20 to 35 Tons Manual de instalación Pagina 24

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 28
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 23
Maintenance
24 CXRC-SVX01F-EN
rise.The maximum allowable rise over a 15 minute period
is 200 microns. If the pressure rise is greater than 200
microns but levels off to a constant value, excessive
moisture is present. If the pressure steadily continues to
rise, a leak is indicated. Figure 19, p. 24 illustrates three
possible results of the “standing vacuum test”.
If a leak is encountered, repair the system and repeat the
evacuation process until the recommended vacuum is
obtained. Once the system has been evacuated, break the
vacuum with refrigerant, and complete the remaining
“Pre-Start Procedures” before starting the unit.
Refrigerant Charging
Important: For proper system operation, use only
refrigerant type listed on unit nameplate.
Once the system is properly installed, leak tested, and
evacuated, refrigerant charging can begin. Charge
refrigerant into the system by weight. Approximate
operating refrigerant charge capacities for 20 through 60-
ton CCRC/CIRC condensing units are given in Table 1, p. 7
Figure 18. Typical vacuum pump hookup
Figure 19. Evacuation time vs. pressure rise
CAUTION
Refrigerant at Freezing Temperature!
Avoid contact with skin. If working with refrigerant is
necessary, you MUST wear all Personal Protective
Equipment (PPE) including eye protection, safety
gloves, long sleeves, and pants. In case of contact, treat
the injury similar to frostbite. Slowly warm the affected
area with lukewarm water and seek immediate medical
attention. Direct contact with liquid refrigerant could
result in minor to moderate injury.
NOTICE:
Compressor Damage!
Charge both circuits of dual circuited systems to
prevent compressor damage.
Vista de pagina 23
1 2 ... 19 20 21 22 23 24 25 26 27 28

Comentarios a estos manuales

Sin comentarios