VRF-SVX28A-EN 27
Configuration
Mode A: Addressing
When digit 2 is set to a value of “A,” unit address settings can be changed. See Figure 7, Figure 8,
and Table 3.
The indoor unit is factory-configured for auto-addressing mode. The factory default address is
0A0000-100000-200000-300000. If the default address is manually changed, the auto-addressing
mode is no longer active.
If the address has been manually changed, and the installer wants to restore auto-addressing
mode, all indoor units in the system must be returned to the initial factory default address.
Figure 7. Address setting mode (digit 2 = A): Digits 2–6
Figure 8. Addressing mode for remote control, Digits 9–12