Troubleshooting
If an error occurs, one of more of the LEDs on the display (see “Components” for their location)
will flicker. As a protection strategy, the unit stops operating (and the LED turns off). If the unit is
turned on before the problem is resolved, the LED will resume flickering and the unit will stop
operating again.
Table 7. Diagnostic LEDs for the mini 4-way cassette indoor unit (continued)
Alarm condition
Error
code
LED display
Power
Defrost
Timer
Filter
Indoor temperature sensor error (shorted or open) E121 Off Flickering Off Off
Evap-in sensor error (shorted or open) E122
Flickering Flickering Off OffEvap-out sensor error (shorted or open) E123
Discharge sensor error (shorted or open) E126
Indoor fan error E154 Off Off Flickering Off
Outdoor temperature sensor error (shorted or open) E221
Flickering Off Flickering OffCondenser sensor error (shorted or open) E237
Discharge sensor error E251
No communication between indoor and outdoor units for 2 minutes E101
Off Flickering Flickering Off
Communication error received from outdoor unit E102
3-minute tracking error on outdoor unit E202
Communication error after tracking due to non-matching quantity of
installed indoor units
E201
Error due to repeated communication address E108
Communication address not confirmed E109
Error due to opened EEV (2nd detection) E151
Off Flickering Flickering Flickering
Error due to closed EEV (2nd detection) E152
Evap-in sensor is loose E128
Evap-out sensor is loose E129
Thermal switch error (open) E198