SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
VariTrane™
Round Inlet/Round Outlet (VRRF)
Installation, Operation,
and Maintenance
Models
VRRF 04-16
VAV-SVN09B-EN
October 2013
Vista de pagina 0
1 2 3 4 5 6 ... 55 56

Indice de contenidos

Pagina 1 - Installation, Operation

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,

Pagina 2 - Environmental Concerns!

Installation10 VAV-SVN09B-ENremoving the old tubing from the airflow switchand using the black tubing provided in the adaptorkit. Connect the airflow

Pagina 3 - Table of Contents

InstallationVAV-SVN09B-EN 11New Facility VRRF Installation(Non-Retrofit)Note: When installing VRRF, make sure the controller islevel so the transducer

Pagina 4 - Model Number Descriptions

Installation12 VAV-SVN09B-ENBinary inputoccupancy or generic (dry contact)Binary outputsAir valve openMaximum output rating forTriac: 12VAAir valve cl

Pagina 5 - General Information

InstallationVAV-SVN09B-EN 13Analog Inputs• AI1• Space temperature; thermistor: 10k  @77°F (25°C)• Range: 32°F to 122°F (0°C to 50°C)• AI2• Space setp

Pagina 6

Installation14 VAV-SVN09B-ENDevice Inputs/OutputsBelow is a list of device inputs and outputs.• Twisted/shielded communication link• Zone sensor• Occu

Pagina 7

InstallationVAV-SVN09B-EN 15See Control Diagrams:• Figure 44 and Figure 45 for the UCM 4.2• Figure 46 and Figure 47 for the VV550• Figure 48 and Figur

Pagina 8

Installation16 VAV-SVN09B-ENair temperature. In order for the auxiliary sensor tofunction as a supply air temperature sensor on VAV unitswith reheat a

Pagina 9 - Adaptor Option Installation

InstallationVAV-SVN09B-EN 17Communication Link WiringUCM VV550Follow these guidelines for Comm5 wiring:• Use 22 AWG unshielded Level 4 communication w

Pagina 10 - Installation

Installation18 VAV-SVN09B-ENAll binary outputs from control board are 24 VAC.Connection points for unit UCM controller are shown inControl Diagrams:•

Pagina 11 - Heavy Objects!

InstallationVAV-SVN09B-EN 19Figure 10. Existing unit with 24-Volt AC coils for electric heat stageSingle Duct Units-Pneumatic Control w/Voltages Great

Pagina 12 - UCM VV550

© 2013Trane All rights reserved VAV-SVN09B-ENWarnings, Cautions and NoticesWarnings, Cautions and Notices. Note that warnings,cautions and notices app

Pagina 13

Installation20 VAV-SVN09B-ENFigure 11. Existing unit with line-voltage coils for electric heat stagesSingle Duct Units-Pneumatic Control w/Voltages 27

Pagina 14 - Power Wiring and Requirements

InstallationVAV-SVN09B-EN 21Figure 12. Pneumatic fan-powered

Pagina 15 - Stand Alone VAV Controls

Installation22 VAV-SVN09B-ENPneumatic Units:Single Duct Hot Water1. Isolate pneumatic hot water valve and remove valvefrom system.2. Install Proportio

Pagina 16 - Communication Link Wiring

InstallationVAV-SVN09B-EN 233. Field wire actuator 24VAC control voltage toVRRF DDCcontroller. See Control Diagrams:a. Figure 44 and Figure 45 for the

Pagina 17

Installation24 VAV-SVN09B-ENFigure 13. SCR motor speed controlFan-Powered Control Box with Electronic or DDC Controls

Pagina 18

InstallationVAV-SVN09B-EN 25Analog and DDC Fan-Powered:Fan-Powered Electric Heat1. Remove Power and Lock and Tag out unit if it hasn'tbeen done a

Pagina 19

Installation26 VAV-SVN09B-ENFigure 14. ECM motor speed control

Pagina 20

InstallationVAV-SVN09B-EN 27Figure 15. Analog duct pressure switch fan control

Pagina 21

Installation28 VAV-SVN09B-ENFigure 16. Analog & DDC fan-powered with electric heatFan-Powered Units-Electronic or DDC/UCMHeater Terminals-Typical

Pagina 22

InstallationVAV-SVN09B-EN 29UCM Programming (UCM 4.2)The UCM 4.2 can be programed usingTracer Summit™,CCP computer software, andTrane’s service tool,

Pagina 23

VAV-SVN09B-EN 3Table of ContentsWarnings, Cautions and Notices ... 2Revision Summary ... 2Trademarks ...

Pagina 24

Installation30 VAV-SVN09B-ENTo Set the Reheat Setup1. Click the ’Configure’ button.2. Click the ’Setup’ tab.3. Click the ’HeatType’ drop-down button a

Pagina 25 - Hazardous Voltage!

InstallationVAV-SVN09B-EN 31To Set the Fan-Powered Setup1. Click the ’Configure’ button.2. Click the ’Setup’ tab.3. Click the ’Fan Type’ drop-down but

Pagina 26

Installation32 VAV-SVN09B-ENTo Set the Set Points1. Click the ’Configure’ button.2. Click the ’Setpoints’ tab.3. Enter the desired settings in the ’He

Pagina 27

InstallationVAV-SVN09B-EN 33UCM VV550The UCMVV550 can be programed usingTracer Summit™computer software, andTrane’s service tool, Rover™.When using Su

Pagina 28

Installation34 VAV-SVN09B-ENTo Set the Reheat Setup1. Click the ’Configure’ button.2. Click the ’Outputs’ tab.3. Click the ’Start’ button.4. Choose th

Pagina 29 - UCM Programming (UCM 4.2)

InstallationVAV-SVN09B-EN 35To Set the Fan-Powered Setup1. Click the ’Configure’ button.2. Click the ’Unit’ tab.3. Choose the desired settings from th

Pagina 30

Installation36 VAV-SVN09B-ENTo Set theTemp Setpoints1. Click the ’Configure’ button.2. Click the ’Unit’ tab.3. Choose the desired settings from the ’S

Pagina 31

InstallationVAV-SVN09B-EN 37UC400 and UC210Navigate to the Configurations Page1. Select Utilities in the tool bar.2. Select Equipment.3. Select Config

Pagina 32

Installation38 VAV-SVN09B-ENSelect VAV control.1. Click the ‘Profile’ drop down box in the ‘ApplicationSelection’ group and select the desired setting

Pagina 33

InstallationVAV-SVN09B-EN 39To set the Fan-Powered Setup 1. Click the ‘Fan Control’ drop down box in the‘Equipment Selection’ group and select the des

Pagina 34

4 VAV-SVN09B-ENModel Number DescriptionsDigits 1-4— Unit TypeVRRF= VariTrane™ Round Inlet andOutlet (Retrofit)Digit 5, 6—Primary Air Valve04 = 4"

Pagina 35

Installation40 VAV-SVN09B-ENTo set the Reheat Setup1. Use the drop down menus in the ‘Reheat Settings’group to choose the desired reheat settings2. Cl

Pagina 36

InstallationVAV-SVN09B-EN 41To setpoints from configuration1. Click the ‘Setpoints’ tab on the toolbarTo Set theTemp Setpoints1. Choose the desired se

Pagina 37 - UC400 and UC210

Installation42 VAV-SVN09B-ENTo setup parameters1. Select Utilities in the tool bar2. Select Equipment3. Select Setup ParametersTo setup parameters fro

Pagina 38

InstallationVAV-SVN09B-EN 43To Set the Flow Setpoints1. Expand the ‘Flow Setpoints Setup’ group2. Choose the desired settings from the ‘Flow Setpoints

Pagina 39

Installation44 VAV-SVN09B-ENTo Set the Measured Value for Airflow1. Expand the ‘VAV Setup’ group2. Choose the desired settings from the ‘VAV Setup’gro

Pagina 40

InstallationVAV-SVN09B-EN 45To Set the Measured Value for AirFlow1. Click the ’Configure’ button.2. Click the ’Setup’ tab.3. Choose the measured value

Pagina 41

Installation46 VAV-SVN09B-ENTo Set the Measured Value for AirFlow1. Click the ’Configure’ button.2. Click the ’Setup’ tab.3. Choose the flow offset an

Pagina 42

VAV-SVN09B-EN 47WiringFigure 44. UCM 4.2 single duct control diagramFactory Installed Harness withField Installed Proportional Water Valve

Pagina 43

Wiring48 VAV-SVN09B-ENFigure 45. UCM 4.2 fan-powered control diagramFactory Installed Harness withField Installed Proportional Water Valve

Pagina 44 - Equipment Damage!

WiringVAV-SVN09B-EN 49Figure 46. VV550 single duct control diagramFactory Installed Harness withField Installed Proportional Water Valve

Pagina 45

VAV-SVN09B-EN 5General InformationThis manual describes the installation of the Round InRound out (VRRF) VAV units with mounting andrecommended wiring

Pagina 46

Wiring50 VAV-SVN09B-ENFigure 47. VV550 fan-powered control diagramFactory Installed Harness withField Installed Proportional Water Valve

Pagina 47 - VAV-SVN09B-EN 47

WiringVAV-SVN09B-EN 51Figure 48. UC400 single duct control diagramFactory Installed Harness withField Installed Proportional Water Valve

Pagina 48 - 48 VAV-SVN09B-EN

Wiring52 VAV-SVN09B-ENFigure 49. UC400 fan-powered control diagramFactory Installed Harness withField Installed Proportional Water Valve

Pagina 49 - VAV-SVN09B-EN 49

WiringVAV-SVN09B-EN 53Figure 50. UC210 single duct control diagram

Pagina 50 - 50 VAV-SVN09B-EN

Wiring54 VAV-SVN09B-ENFigure 51. UC210 fan-powered control diagram

Pagina 52 - 52 VAV-SVN09B-EN

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader increating and sustaining safe, comf

Pagina 53 - VAV-SVN09B-EN 53

6 VAV-SVN09B-ENInstallationDue to their weight and size, VRRF units should besuspended from the uppermost ceiling, independent ofthe false ceiling gri

Pagina 54 - 54 VAV-SVN09B-EN

InstallationVAV-SVN09B-EN 7Figure 2. Round in/round out weights and sizes

Pagina 55

Installation8 VAV-SVN09B-ENNo hanger brackets are provided on these units since theunit should be supported by means of a hanger strap.Thehanger strap

Pagina 56

InstallationVAV-SVN09B-EN 9When installing the VRRF to a pre- existing unit, removepower from pre-existing unit and lock and tag out unit.Remove or pu