Installation
VAV-SVN09B-EN 9
When installing the VRRF to a pre- existing unit, remove
power from pre-existing unit and lock and tag out unit.
Remove or pull back insulation and remove the amount of
inlet ductwork necessary to install the RIRO damper. (See
Figure 2, p. 7 for VRRF lengths.)
Note: Make sure existing VAV unit and inlet ductwork is
adequately supported before removing the section
of ductwork necessary to install VRRF.
Adaptor Option Installation
1. Ensure power has been removed from pre-existing
unit and it has been locked and tagged out.
2. If not already done, begin removing insulation from
the primary air inlet of pre-existing VAV unit.
3. On electric air valves, remove plug connection from J1
terminal and cut plug off of wire and feed wiring from
the control enclosure into the existing unit (See
Figure 3).
Note: Both the control enclosure and existing unit has a
grommet that may need to be removed to get wire
into existing VAV unit.
4. On pneumatic air valves, remove pneumatic tubing
from air valve.
Note: Be aware, on a limited number of units the
pneumatic air valve was too large to remove from
inlet and the hole unit would have to be taken down
to remove the air valve.
5. Remove self tapping screws from air inlet mounting
bracket. In addition, remove pneumatic tubing from
airflow ring. (See
Figure 4)
6. Remove air valve from existing VAV unit by breaking
the seal around air inlet and the VAV unit. Once it is
loose, remove air valve. (See
Figure 5)
7. Clean the surface on existing VAV unit where the air
valve connected to existing VAV unit. Place new
sealant around adapter mounting flange.
8. Mount adapter plate to the existing VAV unit by
aliening the adapter to the proper hole pattern on the
existing VAV unit and screwing in screws. Make sure
that the adaptor is also mounted with hole pattern so
that the VRRF controller is level to the ground. (See
Figure 6)
9. Seal around flange of adapter with duct sealant.
10. Install the Round In / Round Out (VRRF) VAV unit into
adapter making sure control box is level and hang
straps to support VRRF. (See
Figure 1, p. 6 for
Installation and Figure 2, p. 7 for weights)
11. Attach VRRF air valve cylinder to adapter plate using
self-tapping screws.
12. Seal around flange of adapter with duct sealant.
13. Connect inlet ductwork to VRRF and screw in self
tapping screws.
14. Seal around flange of ductwork and VRRF with duct
sealant.
Note: When retrofitting single duct units with electric
heat and series Fan powered pneumatic electric
heat units, the electric heat airflow switch has to
have its input removed from existing air valve and
connected to the new VRRF.This is done by
Figure 3. Remove plug connection
Figure 4. Remove pneumatic tubing
Figure 5. Remove air valve
Figure 6. Adapter mounting