Installation
12 VAV-SVN09B-EN
Binary input
occupancy or generic (dry contact)
Binary outputs
Air valve open
Maximum output rating forTriac: 12VA
Air valve close
Maximum output rating forTriac: 12VA
Heat stage 1:
Maximum output rating forTriac: 12VA
Heat stage 2:
Maximum output rating forTriac: 12VA
Heat stage 3 or Fan output:
Maximum output rating forTriac: 12VA
UCM VV550
Power Requirements
Supply: 18-32 VAC (24VAC nominal) at 50/60 Hz
Operating EnvironmentTemperature:
32 to 140 F (0-60 C)
Relative Humidity
5 to 95% non- condensing
Storage EnvironmentTemperature:
-40 to 185 F
Relative Humidity
5 to 95% non- condensing
Analog inputs
Space temperature
Thermistor
10 K ohms @77 F(25 C)
From 14 to 122 F (-10 to 50 C)
Space setpoint
Potentiometer
1K ohms
From 50 to 90 F (10 to 32.2 C)
Primary discharge air temperature
10 K ohms @77 F(25 C)
From -40 to 212 F (-40 to 100 C)
Primary airflow
Transducer
0-2in. water (0 to 498 Pa)
Binary input
occupancy or generic (dry contact)
Binary outputs
Air valve open
Maximum output rating forTriac: 12VA
Air valve close
Maximum output rating forTriac: 12VA
Heat stage 1:
Maximum output rating forTriac: 12VA
Heat stage 2:
Maximum output rating forTriac: 12VA
Heat stage 3 or Fan output:
Maximum output rating forTriac: 12VA
UC400
Device Inputs/Outputs
Below is a list of device inputs and outputs.
• A twisted/shielded communication link
• Zone sensor
• Occupancy sensor (optional)
• Discharge AirTemperature (DAT) and/or Supply Air
Temperature (SAT)
•CO
2
sensor
• 24 Vac, Class II power
In addition to the points used for the VAV application, the
spare inputs and outputs on the UC400 controller may be
used for ancillary control and programmed usingTracer
TUTracer Graphical Programming 2 (TGP2).
Note: For more information on wiring spare points, refer
to theTracer UC400 Programmable Controller
Installation, Operation, and Maintenance Manual
(BAS-SVX20).
Table 4. UC400 specifications
Storage
Temperature: –48°F to 203°F (–44°C to 95°C)
Relative Humidity: Between 5% and 95% (non-condensing)
Operating
Temperature: –40°F to 185°F (–40°C to 70°C)
Humidity: Between 5% and 95% (non-condensing)
Input Voltage:
20.4–27.6 Vac (24, ±15% nominal), 50Hz to
60Hz
Mounting weight of
controller:
Mounting surface must support 0.80 lb. (.364 kg)
Environmental
rating (enclosure):
NEMA 1
Altitude: 9,842 ft. maximum (3,000 m)
Installation: U.L. 840: Category 3
Pollution: U.L. 840: Degree2
Housing Material:
Polycarbonate/ABS Blend
UV protected
U.L. 94-5VA flammability rating
Mounting:
Mounts on EN 50 022 - 35 X 15 DIN rail that is
included in the VAV unit control box when the
UC400 is factory mounted.
Agency Listing/Compliance
• UL916 PAZX, Open Energy Management Equipment
• UL94-5V, Flammability
• CE Marked
• FCC Part 15, Subpart B, Class B Limit
• AS/NZS CISPR 22:2006
• VCCI V-3/2008.04
• ICES-003, Issue 4:2004
• Communications BACnet MS/TP, supports BACnet protocol ASHRAE
135-2004 and meets BACnet Testing Laboratory (BTL) as an
Application Specific Controller (ASC) profile device UL864/UUKL
listed when installed and programmed in accordance with the Trane
Applications Guide, BAS-APG019-EN.