Installation
VAV-SVN09B-EN 17
Communication Link Wiring
UCM VV550
Follow these guidelines for Comm5 wiring:
• Use 22 AWG unshielded Level 4 communication wire
for most Comm5 installations
• Use shielded Level 4 wire for Comm5Tracker and
VariTrac™ CCP installations
• Always use termination resistors
• Use 105, watt, 1% resistor at each end for Level 4 wire
• Use 82.5, watt, 1% resistor at each end forTrane purple
wire
• Use the daisy chain topology for Comm5 links
• Limit the Comm5 link to 4500 feet
• Limit the link to 60 devices
• Limit zone sensor communication stubs to 8 per link,
50 feet each (maximum)
• Use one repeater for an additional 4500 feet, an
additional 60 devices, and an additional 8
communication stubs
Limit the distance of Comm5 links to 4500 feet. In addition,
limit Comm5 links to 60 devices.The BCU, repeater, and
Rover™ do not count toward this total.
Daisy chain
Although other topologies have been used in the past, we
recommend using only the daisy chain topology on your
Comm5 installations.The likelihood of communication
problems increases with other configurations.
Zone sensor comm stubs
For the most reliable communications, limit the number of
zone sensor communication stubs to 8 per Comm5 link.
Each stub should not exceed 50 feet. Exceeding these
limits increases the likelihood of communication
problems.
Binary Outputs
Wiring to air damper is factory installed but the outputs to
reheat or fan control need to be field installed when
applicable.
Note: All field installed wiring must comply with NEC and
local codes.
11 75 OFF OFF ON OFF ON ON
12 76 ON ON OFF OFF ON ON
13 77 OFF ON OFF OFF ON ON
14 78 ON OFF OFF OFF ON ON
15 79 OFF OFF OFF OFF ON ON
16 80 ON ON ON ON OFF ON
17 81 OFF ON ON ON OFF ON
18 82 ON OFF ON ON OFF ON
19 83 OFF OFF ON ON OFF ON
20 84 ON ON OFF ON OFF ON
21 85 OFF ON OFF ON OFF ON
22 86 ON OFF OFF ON OFF ON
23 87 OFF OFF OFF ON OFF ON
24 88 ON ON ON OFF OFF ON
25 89 OFF ON ON OFF OFF ON
26 90 ON OFF ON OFF OFF ON
27 91 OFF OFF ON OFF OFF ON
28 92 ON ON OFF OFF OFF ON
29 93 OFF ON OFF OFF OFF ON
30 94 ON OFF OFF OFF OFF ON
31 95 OFF OFF OFF OFF OFF ON
32 96 ON ON ON ON ON OFF
33 97 OFF ON ON ON ON OFF
34 98 ON OFF ON ON ON OFF
35 99 OFF OFF ON ON ON OFF
36 100 ON ON OFF ON ON OFF
37 101 OFF ON OFF ON ON OFF
38 102 ON OFF OFF ON ON OFF
39 103 OFF OFF OFF ON ON OFF
40 104 ON ON ON OFF ON OFF
41 105 OFF ON ON OFF ON OFF
42 106 ON OFF ON OFF ON OFF
43 107 OFF OFF ON OFF ON OFF
44 108 ON ON OFF OFF ON OFF
45 109 OFF ON OFF OFF ON OFF
46 110 ON OFF OFF OFF ON OFF
47 111 OFF OFF OFF OFF ON OFF
48 112 ON ON ON ON OFF OFF
49 113 OFF ON ON ON OFF OFF
50 114 ON OFF ON ON OFF OFF
51 115 OFF OFF ON ON OFF OFF
52 116 ON ON OFF ON OFF OFF
53 117 OFF ON OFF ON OFF OFF
54 118 ON OFF OFF ON OFF OFF
55 119 OFF OFF OFF ON OFF OFF
56 120 ON ON ON OFF OFF OFF
57 121 OFF ON ON OFF OFF OFF
Table 8. DIP switch settings (continued)
UCM
Unit #
Eware
Address Dip 1 Dip 2 Dip 3 Dip 4 Dip 5 Dip 6
58 122 ON OFF ON OFF OFF OFF
59 123 OFF OFF ON OFF OFF OFF
60 124 ON ON OFF OFF OFF OFF
61 125 OFF ON OFF OFF OFF OFF
62 126 ON OFF OFF OFF OFF OFF
63 127 OFF OFF OFF OFF OFF OFF