VRF-SVN33A-EN 23
Electrical Wiring
Electrical Wiring
Observe the following precautions when making electrical connections. Refer to wiring diagrams
(Figure 15 and Figure 16).
• Make all electrical connections in accordance with electrical codes and ordinances.
• All wiring must be protected from weather and damage.
• Do not disconnect or change the factory wiring inside the unit.
Figure 15. Typical system installation wiring with internal EEV
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper
conductors could result in equipment damage.
circuit
breaker or
disconnect
Communication between
outdoor and indoor units
Power cable
Indoor unit
Indoor unit
Indoor unit
Ground
Ground
Ground
Wired
remote
controller
Wired
remote
controller
Wired
remote
controller
Ground
Power cable
Communication between
outdoor and indoor units
circuit
breaker or
disconnect
Single-phase, 2-wire, 208-230 V
Mini outdoor unit
Notes:
• Remove burrs from the knock-out hole.
• Use cable conduit and bushing to prevent cables from being
damaged when passing through the knock-out holes.
• Apply rust-resistant paint around the knock-out hole.
See Figure 17, p. 26 for wiring details.