46 VRF-SVN33A-EN
Refrigerant detection operation
Refrigerant detection operation
Perform the refrigerant detection operation only under the following conditions:
• After the unit has been operating in cooling mode for at least 30 minutes.
• Within the following operating envelope:
– Indoor: 68–86°F (20–30°C)
– Outdoor: 41–109.4°F (5–43°C)
Failure to comply may result in the operation ending before completion or in inaccurate results. If
the unit triggers protection control, the results may be inaccurate.
After the refrigerant detection operation is complete, take the following actions:
• If the amount of refrigerant is excessive, discharge 5% of the detected amount and restart the
refrigerant amount detection operation.
• If the amount of refrigerant is insufficient, add 5% of the detected amount and restart the
refrigerant amount detection operation.
• If the degree of supercooling is insufficient, add 10% of the detected amount of refrigerant and
restart the refrigerant detection operation.
• If the result is unavailable, check that the refrigerant detection operation was conducted within
the operating envelope stated above. Perform a test operation to determine if there are any
other problems with the system.
Start
Press the K2 button 4 times
Detect amount of refrigerant
Judge the amount of
refrigerant
Satisfy the temperature
condition
Input VRF Technicial Utili ties signal
End
(Normal) (Excessive) (Insufficient) (Judgment not
available)