Trane Variable Refrigerant Flow System Mini Outdoor Unit Series Manual de instalación Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
VRF-SVN33A-EN 27
Electrical Wiring
Grounding
Important: Grounding must be done by a qualified electrician. The unit cannot be ground by a
gas or water pipe, a lightning rod, or a telephone line grounding wire.
Ground the unit at an exclusive grounding terminal, at the electrical panel (see Figure 18), or—if
the power distribution circuit is not grounded or its grounding does not comply with electrical
codes and specifications—to a grounding rod.
Figure 18. Mini outdoor unit grounding examples
Installing a Grounding Rod
If the installation requires a grounding rod is required, follow this procedure:
1. Select a grounding rod that complies with national and local codes.
2. Select a location for the grounding rod that:
Contains hard damp soil rather than loose sand or gravel.
Is located away from underground structures such as gas and water pipes, telephone lines,
and underground cables.
Is at least 6.6 ft (2 m) away from a lightning conductor.
3. Install the grounding rod in accordance with national and local codes.
4. Proceed with “Installing the Grounding Cable.”
Installing the Grounding Cable
1. Select rated grounding cable by referring to the mini outdoor unit power cable specifications
(Table 11, p. 25).
2. Connect the grounding cable to the grounding hole inside the power supply box and pull it
through the designated grounding knock-out.
Note: If the grounding cable length needs to be extended, make the cable connection in
accordance with national and local codes.
3. If a grounding rod was installed to ground the unit, measure the resistance with a ground
resistance tester. Refer to Table 13 for resistance requirements.
If the resistance is above the requirements, drive the grounding rod deeper into the ground
or increase the number of grounding rods until the resistance requirement is achieved.
Grounded to exclusive
grounding terminal that
is part of the structure
Grounding at the
electrical panel
Grounded to grounding rod