42 VRF-SVN33A-EN
Control System
Monitoring System Settings
Buttons K4 is used to monitor system settings and software versions.
Table 25. Button K4
Number of
times button
K4 is pressed Setting Description
7-segment display
Digits 1, 2, 3, 4
1 Current frequency 15 Hz 1,0,1,5
2
Low pressure
37.0 psi (2.6 kg/cm
2
)
(a)
(a) Gauge pressure
2,0,2,6
3
Outdoor temperature
74.3°F (23.5°C) 3,2,3,5
4
Discharge temperature
177.3°F (80.7°C) 4,8,0,7
5
OLP temperature
203°F (95°C) 5,9,5,0
6
COND Out
temperature 79.3°F (26.3°C) 6,2,6,3
7 Double pipe out tube temperature 113°F (45°C) 7,4,5,0
8 High pressure value 221.9 psi (15.6 kg/cm
2
)
(a)
8,1,5,6
9 Fan speed 700 rpm 9,7,0,0
10 ESC(EVI)EEV 180 step A,1,8,0
11 MAIN EEV 1500 step B,1,5,0
12 Present running current 15 A C,1,5,0
13 Number of connected indoor units 10 D,0,1,0
14 Number of operating mini outdoor units 8 E,0,0,8
15 Sum of indoor unit capacity 47,640 Btu/h (12,000 kcal/h) F,1,2,0
Table 26. Button K4 (press and hold for 3 seconds)
Number of times button K4 is
pressed and held 3 seconds
Software version/
Unit address
7-segment display
Version examples
Digits 1, 2, 3, 4
0
Main circuit board
version
0,9,1,2
1Inverter
board
version
0,9,1,2
2 EEPROM version 0,9,1,2
Digit 1 Digit 2 Digit 3, 4
Address examples
3
Automatically assigned unit
addresses
A00, 5
4
Manually assigned unit
addresses
A00, 1