VRF-SVN33A-EN 37
Control System
Control System
The control board contains a 7-segment display, three DIP switches, two rotary switches, and four
buttons, as shown in Figure 22. Their functions are explained in this section.
Figure 22. Control board
System Monitoring
The 7-segment display indicates system power and communication status.
WARNING
Hazardous Voltage!
Before making contact with the inverter circuit board, wait for at least 15 minutes after
powering down the mini outdoor unit to allow the unit to fully discharge high DC voltage.
Failure to allow the high DC voltage to discharge completely could result in death or serious
injury.
K1 K2 K3 K4
SW01 SW02
7-segment display
K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16
Tens Digit Ones Digit
Table 17. 7-segment display
Event Digit 1 Digit 2 Digit 3 Digit 4
Power up
(a)
8”“8”“8”“8
Establishing
communication between
outdoor and indoor units
A “d” Number of connected indoor units
Transmit/receive
(normal operation)
Indoor unit: “A Indoor unit: “0” Unit address (decimal number)
(a) 7-segment display example showing power-up is shown in Figure 22.