
36 VRF-SVN33A-EN
Connecting the Drain Hose
Connecting the Drain Hose
When using the air conditioner in the heating mode, ice may accumulate. When the unit is in defrost
mode, condensed water must be safely drained away from the unit through a drain hose.
To install the drain hose:
Note: A minimum space of 1.96 in. (50 mm) must be allowed between the bottom of the mini
outdoor unit and the supporting base to facilitate drain hose installation.
1. Insert the drain connector into the drain hole on the underside of the mini outdoor unit.
2. Connect the drain hose to the drain connector.
3. Plug the unused drain holes with drain plugs.
1.96 in. (50 mm)
0.51 in. (13 mm)
Base
Drain hose
Bottom of outdoor unit
Drain
plug
Comentarios a estos manuales