VRF-SVN33A-EN 45
Test Operation
Note: When power is supplied to the outdoor unit, it will check for and verify communications
with the indoor units.
2. Ensure that the front of the outdoor unit is closed.
3. Press and hold button K1 for 5 seconds to run the test operation (see Table 22, p. 41.)
During the test operation, the compressor is restricted from operating.
UP (for “unprepared”) will appear on the digital display. When the test operation has
completed, the display will clear.
The test operation may continue from 30–50 minutes, depending on the operating status.
During the test operation, noise may occur due to valve inspection. (Examine the unit if
abnormal noises continue to occur.)
4. When the test operation ends, use VRF Enterprise Management Software or VRF Auto-
Commissioning Tool to issue a test results report. If any items in the report are marked with an
“inspection required” sign, refer to the service manual for information on correcting the items
and run the test operation again.
5. Ensure the following:
The system has the correct refrigerant amount (see “Refrigerant detection operation” p. 46)
after the unit has been operating in cooling mode for at least 30 minutes
Cooling/heating operation runs normally.
Air flow direction and fan speed of indoor units runs normally.
There are no abnormal operating noises from indoor or outdoor units.
During cooling operation, the indoor units drain properly.
6. Use VRF Enterprise Management Software to check operating status details.
7. Explain to the user how to use the indoor unit and leave them with the indoor unit manual for
their reference.