Trane Variable Refrigerant Flow System Mini Outdoor Unit Series Manual de instalación Pagina 26

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 52
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 25
26 VRF-SVN33A-EN
Electrical Wiring
2. Cut the power cable to an appropriate length and connect it to terminals L and N in the power
supply box with a solderless ring terminal (see Figure 17).
3. If two cables are connected to one terminal, place the cables back to back with the thin cable
upward and the thick cable downward, as shown in the detail in Figure 17.
4. Secure the cable(s) with a cable tie and provide strain relief.
5. Replace the cover on the terminal board.
Note: Make sure that the section of the power supply cable that has the sheath removed is
inside the power supply box. If this is not possible, connect the power cable conduit to
the power supply box.
6. Pull the power cable through the designated knock-out at the bottom right of the mini outdoor
unit (refer to Figure 15, p. 23/Figure 16, p. 24).
Figure 17. Power wiring connections
Screw Tightening torque for terminal Terminals
M4 0.9–1.1 lbf/ft (1.2–1.5 N
.
m) Communication: F1, F2
M5 1.5–1.8 lbf/ft (2.0–2.5 N
.
m) Single-phase AC power: L1, L2
Solderless
ring termina
l
Thin cable
Thick cable
Cable tie
Detail for connec ting
two cables to one terminal
Detail for connec ting
two cables to one terminal
L, N: AC power termina ls
Vista de pagina 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 51 52

Comentarios a estos manuales

Sin comentarios