CAH-SVX01B-EN 25
Installation - Mechanical
TCP Wall Section Assembly
Exterior Wall Assembly (Typical)
1. See Figure 12. Ensure shipping split sections are aligned and pulled together properly.
2. Apply a bead of caulk to full height of wall joint.
3. Apply 3-inch x 1/8-inch adhesive-backed foam gasket to inner joining strip.
4. Install inner joining strip using #14 x 1.5-inch gasketed tec screws.
5. Fit the pre-cut hub cap over the joining strip the vertical height of the wall flush with the roof
and secure it to the wall with # 8 sheet metal screws. Fill the top and bottom openings with caulk
as a moisture seal. Screw holes can be pre-drilled with a #29 bit.
Interior Wall and Roof Joint Assembly (Typical)
1. See Figure 12. Ensure shipping split sections are aligned and pulled together properly.
2. Pre-drill interior joining strip screw holes using #29 drill bit.
3. Apply a bead of caulk the full height of interior wall joint.
4. Install joining strips using #10 sheet metal screws.
Figure 12. Wall section assembly
Add caulking after
installing J strip
#8 x 1-in. Phillips zip screw
2 3/4-in. wide joining strip
Wall split
4-in. x 1/4-in. gasket
Add caulking before
installing J strip
Wall panel section split
2 3/4-in. wide joining strip
Trim cap
#10 x 1-in. self tapping screw
3-in. x 1/8-in. neoprene gasket is
applied to metal joining strip.
Apply gasket to metal strip
before installation.
#8 x 1-in. Phillips zip screw