CAH-SVX01B-EN 81
Start-Up
Traq™ Dampers
Traq dampers are low-leak dampers that modulate and measure airflow. Each Traq damper section
is supplied with a factory-mounted ventilation control module (VCM) on the interior of the mixing
box. The VCM has an input terminal for power and an output terminal for air velocity (see
Figure 76). A direct-digital controller controls the factory-mounted and wired actuators.
VCM (Transducer) Calibration. The VCM has an auto-zero function that recalibrates the
transducer once every minute. When troubleshooting, allow for the recalibration time before
making any measurements.
Input Power. The only input the VCM needs is the 24 Vac power connected to terminals 1TB1–5
and 1TB1–6.
Output Velocity Signal. The 2 to 10 Vdc linear output signal from the VCM represents air
velocity. This voltage can be converted to represent airflow (cfm or L/s) using the formula below,
Tab le 5 and Tab le 6.
In Table 6 the cfm at 10Vdc is a calculated value based on area and peak velocity. In certain
situations, it can be advantageous to raise the velocity of air through the remaining Traq dampers
by closing off one or more dampers in the unit. The cfm at 10Vdc can be recalculated based on the
proportion of remaining Traq dampers or by multiplying the remaining area of dampers by peak
velocity.
Figure 76. Traq damper terminal connections
Ventilation Control Module
Velocity (2-10 Vdc)
GND
24 Vac
GND
1TB1-3
1TB1-4
1TB1-5
1TB1-6
Table 5. Altitude adjustment factors
Airflow = k (cfm @ 10V)
or
Airflow = k (L/s @ 10V)
For example, if the VCM on a size 30 air handler at sea level (k=1)
has a 10-volt signal, it would represent 17,335 cfm
(8181 L/s) through the Traq damper. If the voltage were 6 volts,
airflow through the Traq damper would be 8,668 cfm (4091 L/s).
Sea level = 1.0
Elevation (feet) k
1000 0.982
2000 0.964
3000 0.949
4000 0.930
5000 0.914
6000 0.897
7000 0.876
8000 0.860
9000 0.846
10,000 0.825
volts 2()
8
------------------------------
volts 2()
8
------------------------------