Trane Performance Air Handlers Manual de instalación Pagina 26

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 25
26 CAH-SVX01B-EN
Installation - Mechanical
TCP Outdoor Roof Assembly - Single Span
1. Ensure shipping split sections are aligned and pulled together properly. See Figure 13.
2. Add a bead of caulk along the length of the roof seams. Install the pre-cut J-cap over the seam
and secure with #14 sheet metal screws on 12-inch centers.
Note: Use a polyurethane or equivalent caulk. It may be necessary to clamp the joint together or
pre-drill to prevent separation when drilling with screws.
3. Apply caulk to end of J-cap to seal thoroughly.
Figure 13. TCP outdoor roof assembly - single span
Add caulking before
installing J cap
Joining cap
4-in. x 1/4-in. gasket
#10 x 1-in. self-tapping screw
Roof panel
section split
2 3/4-in. wide joining strip
#8 x 1-in. Phillips zip screw
3-in. x 1/8-in. neoprene gasket is
applied to metal joining strip.
Apply gasket to metal strip
before installation.
Roof split outdoor unit
Vista de pagina 25