Trane Performance Air Handlers Manual de instalación Pagina 37

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 100
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 36
CAH-SVX01B-EN 37
Installation - Mechanical
TCC Wall Section Assembly (Typical)
1. Verify external unit squareness.
2. To complete the exterior joint, install a bead of caulk full height of side panel joint.
3. Over caulk, install 3/16-inch x 1.25-inch ribbed grey butyl the full height of the side panel up to
underside of roof overhang. Leave the paper backing on this tape, sealing the joint does not
require this to be removed. The paper will be facing out towards seam cap.
4. Install side seam cap over butyl tape and secure with #10-16 x 0.750 self-drilling screw. The
bottom two screws on this seam cap will be larger, ¼ x 20 self drillers with neoprene gasket (see
Figure 30).
TCC Indoor Roof Section Assembly (Typical)
1. Verify external unit squareness.
2. Apply the 1.25-inch x 0.33-inch ribbed butyl tape to the exterior of the roofs covering the seam
of the two adjoining sections (see method sheet).
3. Install seam cap over the butyl, uniformly straddling the splits. Secure with the provided
number 10 sheet metal screws. See Figure 30.
Figure 30. Install seam cap over the butyl tape
A
DETAIL A
Screw 10-16 x .750 self-driller
Screw 10-16 x .750
self-driller
Screw 10-16 x .750 self-driller
2 Screws .250-14 x 1.00 Hes WSH HD self-driller
Butyl tape
Seam cap
Seam cap
Butyl tape
Joint cap