CAH-SVX01B-EN 55
Coil Piping and Connections
Figure 50. Drain pan trapping for section under negative pressure
Figure 51. Drain pan trapping for section under positive pressure
Normal operation
L
H
J
L = H + J + pipe diameter
where:
H = 1 inch for each inch of negative
pressure* plus 1 inch
J = 1/2 H
*Negative pressure = total unit static
pressure at worst case (loaded filters)
minus external pressure
K
H
L
L = H + K + pipe diameter
where:
K = 1/2 inch (minimum)
H = 1/2 inch plus the total unit
static pressure at worst case
(loaded filters)