52 CAH-SVX01B-EN
Installation - Mechanical
Outdoor Unit Weather Hood(s)
1. Per the unit drawing determine mounting location of the unit weather hoods.
2. Using the factory provided screws mount the weather hoods to the unit.
3. On larger units, weather hoods may be large enough to require angled down supports. In those
cases, the angles are shipped attached to the hood but will need to be connected to the air
handler by the installing contractor. See Figure 49.
Note: It is required that the hoods be sealed to the unit using field provided caulk or gasket.
Figure 49. Hood installation
AHU outdoor roof
Butyl caulk tape
1.00 W x .125T.
Hood
Nut-Hex .31-18
Detail A
Screw self-driller
10-16 x .750
Butyl caulk tape
1.00 W x .125T.
Nut-Hex .31-18
Bolt .313-18 x .750 Hex
Bracket Support
Angle Hood Support
(when required)
Bolt .313-18 x .750 Hex
Vista de pagina 51