Vista de pagina 105
106 VAV-PRC011M-EN
DDC Controls
Resolution of Analog Outputs
10 ppm CO
2
Power Supply
Nominal 24 VAC
Power Consumption
<5 VA
Housing Material
ABS plastic
Dimensions
4 1/4" x 3 1/8" x 1 7/16" (Wall only)
(108 mm x 80 mm x 36 mm) (Wall only)
3 1/8" x 3 1/8" x 7 ¾"
(80 mm x 80 mm x 200 mm)
DDC Zone Sensor with LCD
Specifications
Thermistor Resistance Rating
10,000 Ohms at 77°F (25
o
C)
Setpoint Resistance Rating
Setpoint potentiometer is calibrated to produce 500 Ohms at a setting of 70
o
F (21.11
o
C)
Temperature Range
Displays 40 to 99
o
F (5 to 35
o
C)
With Setpoints 50 to 90
o
F (10 to 32
o
C)
Electrical Connections
Terminal Block – Pressure Connections
Communication Jack – WE – 616
4 VA maximum power input.
Physical Dimensions
Width: 2.8" (71.12 mm)
Length: 4.5" (114.3 mm)
Height: 1.1" (27.94 mm)
The DDC zone sensor with LCD has the look and functionality of the
standard Trane DDC zone sensor but has a LCD display. The sensor
includes setpoint adjustment, the display of the ambient temperature, a
communication jack, and occupied mode override pushbuttons. Also, it
can be configured in the field for either a Fahrenheit or Celsius display, a
continuous display of the setpoint and the offset of displayed
temperatures.