Vista de pagina 21
22 VAV-PRC011M-EN
Single-Duct VAV Terminal Units
Table 5. Air pressure drop - Pa (SI)
Inlet Size Airflow (L/s) Cooling Only
Hot Water
1-row coil
Hot Water
2-row coil
Hot Water
3-row coil
Hot Water
4-row coil Electric Heat
04
25
50
70
105
3
3
3
3
3
4
7
15
3
4
7
15
2.5
7.5
20
40
2.5
10
25
55
3
3
3
3
05
45
95
140
165
3
3
3
4
3
12
22
29
6
21
41
54
7.5
32
67
87
10
45
90
117
3
3
5
6
06
45
120
165
235
3
13
26
55
4
29
55
112
7
43
79
155
7.5
50
87
159
10
65
117
212
3
14
27
57
08
95
190
280
420
3
4
9
21
8
25
49
99
13
43
83
169
17
60
122
242
22
80
159
319
3
6
12
28
10
235
375
520
660
3
3
3
3
16
37
67
104
29
63
110
165
42
95
164
247
55
127
219
329
3
5
9
13
12
375
565
755
940
3
3
3
3
24
47
76
111
47
88
138
195
55
105
172
252
70
139
227
334
3
7
13
19
14
700
945
1180
1415
3
3
3
3
26
40
56
74
55
89
127
171
85
135
197
272
110
179
262
361
3
3
3
3
16
940
1180
1415
1885
3
3
3
3
28
40
54
87
73
114
162
284
97
142
194
321
130
189
259
428
3
4
5
8
24 x 16
1885
2600
3070
3775
20
40
57
90
100
176
236
341
165
279
366
513
242
431
593
902
321
573
790
1203
38
76
110
172
Notes:
1. Hot water pressure drops are for the entire unit, not just the coil. To calculate the hot water coil only pressure drop, subtract the cooling only
pressure drop from the other pressure drop.
ABCD
HF
E
J
A,B,C III
I, II
III, IV
IV
I, II I, II
OUTL
H
J
D,E,F
N/A
I, II
I, II
N/A
I, II
I, II
N/A
I, II
I, II
I, II, III
N/A
I, II, III
II, III, IV
I
II, III, IV
III, IV
I, II
III, IV
OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINALØ
VALV 4
OUTL CONVERSION CHART
NOMINALØ
5" (127 mm)
6" (152 mm)
8" (203 mm)
10" (254 mm)
IV
56
SYMBOL
II
III
I
81012
OUTLET PLENUM
ARRANGEMENTS