134 VAV-PRC011M-EN
Controls Specifications
For all VariTrane™ units, the unit controller continuously monitors the zone temperature and varies
the primary airflow as required to meet zone setpoints. Airflow is limited by adjustable minimum
and maximum setpoints.
Additionally, for series fan-powered units, the controller will start and run the fan continuously
during the occupied mode and intermittently during the unoccupied mode. Upon a further call for
heat, any hot water or electric heat associated with the unit is enabled.
For parallel fan-powered units, the controller energizes the fan upon a call for heat. Upon a further
call for heat, reheat is enabled.
Direct Digital Controls (DDC)
LONMARK Direct Digital Controller
Trane-designed L
ONMARK
®
certified controller uses the space comfort control (SCC) profile to
exchange information over a LonTalk™ Network. LonMark networks provide the latest open
protocol technology.
Direct Digital Controller
The microprocessor-based terminal unit controller provides accurate, pressure-independent
control through the use of a proportional integral control algorithm and direct digital control
technology. The UCM, monitors zone temperature setpoints, zone temperature, the rate of
temperature change, and valve airflow. With the addition of optional sensors, room occupancy or
supply duct air temperature can be monitored. The controller is provided in an enclosure with 7/
8” (22 mm) knockouts for remote control wiring. A Trane DDC zone sensor is required.
DDC Actuator
Trane 3-wire, 24-VAC, floating-point quarter turn control actuator with linkage release button.
Actuator has a constant drive rate independent of load, a rated torque of 35 in-lb, a 90-second drive
time, and is non-spring return. Travel is terminated by end stops at fully opened and closed
positions. An integral magnetic clutch eliminates motor stall.
DDC Actuator - Belimo
LMB24-3-T TN 3-wire, 24 VAC/DC, floating-point, quarter turn actuator with linkage release button.
Actuator has a constant drive rate independent of load, a rated torque of 45 in-lb, a 95 second drive
time, and is non-spring return. Travel is terminated by end stops at fully-opened and -closed
positions. Internal electronic control prevents motor stall when motor reaches end stops.
DDC Zone Sensor
The UCM controller measures zone temperature through a sensing element located in the zone
sensor. Other zone sensor options may include an externally-adjustable setpoint, communications
jack for use with a portable service tool, and an override button to change the individual controller
from unoccupied to occupied mode. The override button has a cancel feature that will return the
system to unoccupied. Wired zone sensors utilize a thermistor to vary the voltage output in
response to changes in the zone temperature. Wiring to the UCM controller must be 18 to 22 awg.
twisted pair wiring. The setpoint adjustment range is 50–88ºF (10–31°C) Depending upon the
features available in the model of sensor selected, the zone sensor may require from a 2-wire to
a 7-wire connection. Wireless zone sensors report the same zone information as wired zone
sensors, but do so using radio transmitter technology. No wiring from the zone sensor to the UCM
controller is necessary.
Digital Display Zone Sensor with Liquid Crystal Display (LCD)
The direct digital zone sensor contains a sensing element which sends a signal to the UCM. A Liquid
Crystal Display (LCD) indicates setpoint, or space temperature. Sensor buttons allow setpoint
adjust, and allow space temperature readings to be turned on or off. The digital display zone sensor
also includes a communication jack, for use with a portable edit device, and an override button to
change the UCM from unoccupied to occupied. The override button has a cancel feature, which