VAV-PRC011M-EN 77
Dual-Duct VAV Terminal Units
Air Valve Round — The primary air inlet connection is an 18-gage galvanized steel cylinder sized
to fit standard round duct. A multiple-point, averaging flow sensing ring is provided with balancing
taps for measuring +/-5% of unit cataloged airflow.
An airflow-versus-pressure differential calibration chart is provided. The damper blade is
constructed of a closed-cell foam seal that is mechanically locked between two 22-gage galvanized
steel disks. The damper blade assembly is connected to a cast zinc shaft supported by self-
lubricating bearings. The shaft is cast with a damper position indicator. The valve assembly
includes a mechanical stop to prevent over-stroking. At 4.0 in. wg, air valve leakage does not exceed
1% of cataloged airflow.
Outlet Connection
Slip & Drive Connection—Terminal units come standard with slip & drive connection.
Outlet Plenum/Attenuator—A sheet metal, insulated plenum/attenuator with circular opening(s)
is attached to the discharge of the main unit at the factory. The circular opening(s) are centered on
the unit plenum to accept round ductwork connections.
Outlet Plenum/Attenuator with Balancing Dampers—A sheet metal, insulated plenum/attenuator
with circular opening(s) is factory-connected to the main unit. The circular opening(s) with
balancing damper(s) are centered on the unit plenum to accept round ductwork connections.
Unit Controls Sequence of Operation
Unit controller continuously monitors zone temperature against its setpoint and varies primary
airflow as required to meet zone setpoints. Airflow is limited by minimum and maximum position
setpoints.
Direct Digital Controls
DDC Actuator—Trane 3-wire, 24-VAC, floating-point quarter turn control actuator with linkage
release button. Actuator has a constant drive rate independent of load, a rated torque of 35 in-lb,
a 90-second drive time, and is non-spring return. Travel is terminated by end stops at fully-opened
and -closed positions. An integral magnetic clutch eliminates motor stall.
DDC Actuator - Belimo — LMB24-3-T TN 3-wire, 24 VAC/DC, floating-point, quarter turn actuator
with linkage release button. Actuator has a constant drive rate independent of load, a rated torque
of 45 in-lb, a 95 second drive time, and is non-spring return. Travel is terminated by end stops at
fully-opened and -closed positions. Internal electronic control prevents motor stall when motor
reaches end stops.
Direct Digital Controller—The microprocessor based terminal unit controller provides accurate,
pressure-independent control through the use of a proportional integral control algorithm and
direct digital control technology. The controller, named the Unit Control Module (UCM), monitors
zone temperature setpoints, zone temperature and its rate of change, and valve airflow using a
10 (254) 1400 (661) 08 (203) 900 (425)
10 (254) 1400 (661) 10 (254) 1400 (661)
12 (305) 1400 (944) 08 (203) 900 (425)
12 (305) 2000 (944) 10 (254) 1400 (661)
12 (305) 2000 (944) 12 (305) 2000 (944)
14 (356) 3000 (1416) 14 (356) 3000 (1416)
16 (406) 4000 (1888) 16 (406) 4000 (1888)
Table 47. Air valve combinations available (continued)
Air Valve Size in. (mm)
Cooling
Cataloged Airflow cfm
(L/s)
Cooling
Air Valve Size in. (mm)
Heating
Catalog Airflow cfm
(L/s)
Heating
05 (127) 350 (165) 05 (127) 350 (165)