Trane Round In/Round Out Lista de partes Pagina 146

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 158
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 145
146 VAV-PRC011M-EN
Application Considerations
Flow Measurement and Control
The differential pressure signal output of the flow ring provides the terminal unit controller a
measurement of the primary airflow through the inlet. The terminal unit controller then opens or
closes the inlet damper to maintain the controller airflow setpoint
Flow Measurement
Most VAV terminal units contain a differential pressure airflow measurement device, mounted at
the primary air inlet, to provide a signal to the terminal unit controller. Numerous names exist for
the differential pressure measurement device—flow sensor, flow bar, flow ring. The differential
pressure measured at the inlet varies according to the volumetric flow rate of primary air entering
the inlet.
The total pressure and the static pressure are measurable quantities. The flow measurement
device in a VAV terminal unit is designed to measure velocity pressure. Most flow sensors consist
of a hollow piece of tubing with orifices in it. The VariTrane air valve contains a flow ring as its flow
measuring device. The flow ring is two round coils of tubing. Evenly spaced orifices in the upstream
coil are the high-pressure taps that average the total pressure of air flowing through the air valve.
The orifices in the downstream ring are low-pressure taps that average the air pressure in the wake
of flow around the tube. By definition, the measurement of static pressure is to occur at a point
perpendicular to the airflow. The low-pressure taps on the VariTrane flow ring measure a pressure
that is parallel to the direction of flow but in the opposite direction of the flow. This “wake pressure”
that the downstream ring measures is lower than the actual duct static pressure. The difference
between the “wake pressure” and the static pressure can be accounted for so that the above
relationship between flow and differential pressure remain valid. The difference also helps create
a larger pressure differential than the velocity pressure. Since the pressures being measured in VAV
terminal box applications are small, this larger differential allows transducers and controllers to
measure and control at lower flow settings than would otherwise be possible.
The average velocity of air traveling through the inlet is expressed in the equation:
Where:
Often, the density is assumed to be a constant for dry air at standard conditions (68°F (20°C)) and
sea level pressure of 14.7 psi (101.4 kPa)). These conditions yield the following commonly used
equation:
The velocity pressure is defined as the difference between the total pressure in the duct and the
static pressure in the duct:
One of the most important characteristics of a VAV terminal unit is
its ability to accurately sense and control airflow. The VariTrane
terminal unit was developed with exactly that goal in mind. The
patented, multiple-point, averaging flow ring measures the
velocity of the air at the unit primary air inlet.
FPM = Velocity of air in feet per minute
1096.5 = A constant
VP = The velocity pressure of the air expressed in inches of water
DENS = The density of the air expressed in pounds per cubic foot
FPM 1096.5
VP
DENS
------------------=
FPM 4005 VP=
Vista de pagina 145
1 2 ... 141 142 143 144 145 146 147 148 149 150 151 ... 157 158

Comentarios a estos manuales

Sin comentarios