Trane Round In/Round Out Lista de partes Pagina 83

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 158
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 82
VAV-PRC011M-EN 83
DDC Controls
wall fin radiation, convector, etc.) or any combination of local and remote. The operating
characteristics of the four basic types of VariTrane DDC terminal reheat are discussed.
Single-Duct: On/Off Hot Water Reheat
Three stages of on/off hot water reheat are available. Two-position water valves complete the HW
reheat system and are either fully opened or fully closed. The heating minimum airflow setpoint
is enforced during reheat.
Stage 1 energizes when the space temperature is at or below the heating setpoint. When the zone
temperature rises above the active heating setpoint by 0.5°F (0.28°C), stage 1 is de-energized. Stage
2 energizes when the space temperature is 1°F (0.56°C) or more below the active heating setpoint,
and is de-energized when the space temperature is 0.5°F (0.28°C) below the active heating setpoint.
Stage 3 energizes when the zone temperature is 2°F (1.11°C) or more below the active heating
setpoint, and de-energizes when the space temperature is 1.5°F (0.83°C) below the active heating
setpoint. When reheat is de-energized, the cooling minimum airflow setpoint is enforced.
Single-Duct: Proportional Hot Water Reheat
Proportional hot water reheat uses 3-wire, floating-point-actuator technology.
When the space temperature drops below the active heating setpoint, the air valve open to the
Airflow Setpoint Reset Minimum Local Heat and the reheat valve modulates to maintain space
temperature at the active heating setpoint. Control of the water valve uses a separate proportional
plus integral control loop, and its position is dependent on the degree that the space temperature
is below the active heating setpoint and the amount of time that the space temperature has been
below the active heating setpoint.
If the discharge air temperature reaches the Discharge Air Temperature Design Setpoint, the air
valve opens further and modulates between Airflow Setpoint Reset Minimum Local Heat and
Airflow Setpoint Reset Maximum Local Heat to maintain space temperature at the active heating
setpoint, while the water valve modulates to maintain discharge air temperature at the Discharge
Air Temperature Design Setpoint. If the air valve reaches Airflow Setpoint Reset Maximum Local
Heat, the water valve opens further and modulates to maintain space temperature at the active
heating setpoint, while the air valve remains at Airflow Setpoint Reset Maximum Local Heat.
An additional on/off remote heat output is available and energized when the water valve is driven
100% open and de-energized when the water valve reaches 50% open.
In the event that the DAT sensor fails, or is not connected, when the space temperature drops below
the active heating setpoint, the air valve open to the Airflow Setpoint Minimum Local Heat and the
water valve modulates to maintain space temperature at the active heating setpoint.
When reheat is de-energized, the cooling Airflow Minimum Setpoint is enforced.
Single-Duct: On/Off Electric Reheat
One, two, or three stages of staged electric reheat are available. The heating minimum airflow
setpoint is enforced during reheat.
Stage 1 is energized when the space temperature falls below the active heating setpoint and
minimum airflow requirements are met. When the zone temperature rises above the active heating
setpoint by 0.5°F (0.28°C), stage 1 is de-energized. Stage 2 energizes when the space temperature
is 1°F (0.56°C) or more below the active heating setpoint, and is de-energized when the space
temperature is 0.5°F (0.28°C) below the active heating setpoint. Stage 3 energizes when the zone
temperature is 2°F (1.11°C) or more below the active heating setpoint, and de-energizes when the
space temperature is 1.5°F (0.83°C) below the active heating setpoint. When reheat is de-energized,
the cooling minimum airflow setpoint is enforced.
Single-Duct: Pulse-Width Modulation of Electric Heat
One to three stages of pulse-width modulation of electric heat are available. Energizing for a
portion of a three-minute time period modulates the electric heater. This allows for closer matching
Vista de pagina 82
1 2 ... 78 79 80 81 82 83 84 85 86 87 88 ... 157 158

Comentarios a estos manuales

Sin comentarios