18 VAV-PRC011M-EN
Single-Duct VAV Terminal Units
Air pressure drop (APD) of the hot water coil is included in the chart preceding the hot water coil
performance data section.
APD = 0.35 in. wg
Electric Heat
Determine the kW required to meet zone design heat loss.
kW=MBh / 3.414
MBh=Design Heat Loss
Select the nearest available kW with voltage and steps desired from the electric heater kW guideline
table in the Performance Data section of the catalog.
Example
VCEF, Electric Unit Heat, Size 12 (See Air Valve Selection)
Heating airflow: 850 cfm
Voltage: 277/60/1 VAC
Design Heat Loss: Q=25 MBh
kW=Q/3.414
kW=25/3.414
kW=7.3
Selection:
Select 7.5 kW from the electric heat table in the voltage and stages required. The table shows the
minimum cfm allowable for the kW selected. The static pressure requirement is shown as 0.06 in.
wg for this example with a design cooling flow of 1700 cfm.
Check Leaving Air Temperature:
T is the primary entering air temperature 55°F for this example.
Decide if leaving air temperature of 82.8°F is satisfactory for your application.
Acoustics
The acoustical data found in the "Performance Data" section of the VAV catalog is used to make a
determination of the amount of noise the terminal unit will generate. Locate the table for the VAV
terminal unit of interest. Sound power data and an equivalent NC level for an AHRI 885-2008
transfer function is listed.
Example
VCCF, Cooling-Only Terminal Unit, Size 10 (See air Valve Selection)
Cooling Airflow: 1100 cfm
Maximum inlet static pressure: 1.5 in. wg
Interpolation gives sound power data of:
The NC level above is determined by using either the catalog’s AHRI 885-2008 mineral fiber for
radiated sound transfer function for the conditions shown in the acoustics table. A different transfer
function could be applied as conditions dictate.
LAT
Q
1.085 CFM×
-------------------------------------
T+=
LAT
3414 7.5×
1.085 850×
-----------------------------------
55 82.8=+=
Octave Band 2 3 4 5 6 7 NC
Disch Sound Power 68686565 605728
Rad Sound Power 63 58 54 47 39 32 29