Trane Round In/Round Out Lista de partes Pagina 148

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 158
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 147
148 VAV-PRC011M-EN
Application Considerations
Linearity
With the increase in DDC controls over pneumatic controls, the issue of linearity is not as great as
it once was. The important aspect of flow measurement versus valve position is the accuracy of
the controller in determining and controlling the flow. Our units are tested for linearity and that
position versus airflow curve is downloaded and commissioned in the factory to insure proper
control of the unit.
Reheat Options
Hot water heating coils are generally applied on VAV terminal units as reheat devices. When
applying these coils it is important to make sure that they are operating in the proper air flow and
water flow range. Either a two-way or a three-way valve controls the coils.
The most important factor when sizing valves is the coefficient of velocity or C
v
. The C
v
is defined
as the flow rate, in gallons of 60°F (15.56°C) water, that will pass through the valve in one minute
with a one pound pressure drop. The coefficient of velocity, which is commonly called the flow
coefficient, is an industry standard rating. Valves having the same flow coefficient rating,
regardless of manufacturer, will have the same waterside performance characteristics.
The equation that governs valve sizing is:
Where
C
v
=Flow coefficient
GPM=The maximum water flow rate through the valve in gallons per minute
DP=The maximum allowable differential pressure across the valve in psi
The flow and differential pressure are generally the known quantities. The equation is solved for
the flow coefficient. The flow coefficient is then compared to the published C
V
values for the control
valves that are available. The control valve with the C
V
that is the closest, but greater than, the
calculated flow coefficient is the correct choice for the control valve. This choice will keep the valve
pressure drop below the maximum allowable valve pressure drop. The valve pressure drop should
then be checked against the coil pressure drop. If the coil pressure drop is appreciably larger than
the valve pressure drop, a valve with a smaller C
V
should be selected to produce a larger control
valve pressure drop. If this new valve has a pressure drop that is much larger than the maximum
allowable pressure drop for valves, the system designer should be consulted to make sure that the
system hot water pumps can deliver the water at the new conditions.
Figure 15. Hot water coil (L) & hot water valves (R)
C
v
GPM
ΔP
--------------
=
Vista de pagina 147
1 2 ... 143 144 145 146 147 148 149 150 151 152 153 ... 157 158

Comentarios a estos manuales

Sin comentarios