VAV-PRC011M-EN 35
Single-Duct VAV Terminal Units
Table 22. Heating capacity (kW) - inlet size 14 (SI)
Water
Pressure
Drop (kPa)
Airflow (L/s)
Rows L/s 283 472 661 849 1038 1227 1416 1604 1793 1888
1-Row
Capacity
kW
0.13 3.37 7.43 9.44 10.96 12.23 13.28 14.19 14.97 15.67 16.29 16.66
0.19 7.02 7.89 10.23 12.04 13.54 14.88 16.07 17.13 18.08 18.94 19.47
0.25 11.85 8.14 10.67 12.66 14.36 15.85 17.18 18.42 19.55 20.58 21.22
0.32 17.81 8.30 10.96 13.07 14.89 16.50 17.96 19.29 20.53 21.69 22.41
0.38 24.89 8.41 11.16 13.36 15.27 16.97 18.52 19.95 21.26 22.49 23.27
0.44 33.04 8.49 11.30 13.57 15.55 17.33 18.95 20.44 21.83 23.12 23.94
2-Row
Capacity
kW
0.32 3.05 11.43 16.52 20.09 22.75 24.83 26.50 27.87 29.03 30.03 30.61
0.57 9.35 11.93 17.74 22.07 25.46 28.20 30.47 32.39 34.04 35.49 36.35
0.82 18.93 12.13 18.25 22.93 26.66 29.72 32.29 34.50 36.42 38.10 39.12
1.07 31.73 12.24 18.53 23.41 27.33 30.59 33.35 35.73 37.81 39.65 40.76
1.33 47.69 12.30 18.71 23.71 27.77 31.16 34.04 36.53 38.72 40.67 41.85
1.45 56.86 12.33 18.78 23.83 27.94 31.37 34.30 36.84 39.07 41.06 42.26
3-Row
Capacity
kW
0.32 3.70 12.76 19.01 23.54 26.97 29.65 31.82 33.62 35.13 36.42 37.18
0.44 6.96 13.04 19.78 24.87 28.85 32.06 34.70 36.93 38.84 40.49 41.48
0.57 11.17 13.19 20.22 25.65 29.98 33.52 36.48 39.01 41.19 43.09 44.24
0.69 16.33 13.29 20.51 26.16 30.73 34.50 37.69 40.43 42.80 44.90 46.16
0.82 22.40 13.36 20.71 26.53 31.26 35.21 38.56 41.46 43.99 46.22 47.57
0.95 29.40 13.41 20.86 26.80 31.66 35.74 39.23 42.24 44.89 47.24 48.66
0.95 29.40 13.41 20.86 26.80 31.66 35.74 39.23 42.24 44.89 47.24 48.66
1.20 46.10 13.48 21.07 27.18 32.23 36.50 40.16 43.36 46.18 48.69 50.22
1.33 55.80 13.51 21.14 27.31 32.43 36.77 40.51 43.77 46.66 49.23 50.80
1.45 66.38 13.53 21.20 27.43 32.61 37.00 40.80 44.12 47.06 49.68 51.29
4-Row
Capacity
kW
0.32 4.36 14.00 21.55 27.17 31.45 34.82 37.52 39.74 41.60 43.18 44.11
0.44 8.13 14.24 22.33 28.64 33.65 37.71 41.07 43.90 46.31 48.40 49.64
0.57 12.99 14.37 22.76 29.47 34.93 39.44 43.23 46.47 49.27 51.72 53.18
0.69 18.92 14.45 23.03 30.01 35.77 40.59 44.68 48.21 51.29 54.00 55.64
0.82 25.88 14.50 23.22 30.39 36.36 41.40 45.72 49.47 52.76 55.68 57.44
0.95 33.87 14.55 23.36 30.67 36.80 42.01 46.50 50.42 53.88 56.95 58.82
1.07 42.88 14.57 23.47 30.88 37.13 42.48 47.11 51.17 54.75 57.95 59.90
1.20 52.89 14.60 23.55 31.05 37.40 42.86 47.60 51.77 55.46 58.76 60.78
1.33 63.91 14.61 23.62 31.19 37.63 43.17 48.00 52.26 56.04 59.43 61.51
1.45 75.91 14.63 23.67 31.30 37.81 43.43 48.34 52.67 56.53 59.99 62.12
Note: Refer to the Hot Water Reheat & Coil Notes (SI) at the end of the Performance Data section for fouling factors and LAT/WTD calculating equations.